Acid-Detector is a test kit designed for use in the field to detect acid in air-conditioning and refrigeration oils. It quickly and accurately detects unacceptable amounts of acids which may be present in all mineral and alkylbenzene type refrigeration oils.

Acid-Detector is easy to use and quickly detects acid without having to wait days or weeks for a laboratory analysis.
Top of Page

CHARACTERISTICS:


  • Accurate
  •  Quick
  • Easy to use
  • Saves time and money
  • Top of Page

    APPLICATIONS:


    Acid-Detector may be used with all mineral and alkylbenze type refrigerant oils. Designed to provide quick and accurate oil analysis while in the field. May be used on all systems both refrigeration and air conditioning.

    Top of Page

    PACKAGING:


     Code Qty. Per Case Lbs. per Case Cu. Ft Per Case
    45002

     12 boxes

    3 .22

    Top of Page

    INSTRUCTIONS:


    1. Pour contents of smaller bottle into larger bottle. The bottom layer of new mixture will turn purple in color.

    2. Completely fill small bottle with oil being tested.

    3. Pour small bottle of oil into the larger bottle, cap and shake well.

    4. Within a few minutes a two layer phase separation will develop. If the bottom layer loses its purple color, the sample oil has an acid number of 0.05 or higher.

    5. Systems with acid levels higher than 0.05 should be cleaned and treated with ACID-AWAY®.

    For additional technical information, call Toll Free 1-800-231-3345.

    Top of Page

    PRECAUTIONS:


    FOR CHEMICAL EMERGENCY, SPILL, LEAK, FIRE, EXPOSURE OR ACCIDENT,

    CALL CHEMTREC - DAY OR NIGHT 1-800-424-9300

    D  A  N  G  E  R!
     
    FLAMMABLE - POISON!

    CONTAINS: Methanol and Toluene. Cannot be made non-poisonous. PRECAUTIONS: Vapors harmful. May be fatal or cause blindness if swallowed. May cause eye and skin irritation. Keep away from heat, sparks, and flames. Use with adequate ventilation.Wash thoroughly after use. FIRST AID: For any overexposure, get immediate medical attention after first aid is given. Eyes and Skin - Flush with large amounts of clean water for at least 15 minutes. Inhalation - Remove to fresh air. Ingestion - Only if conscious, give large amounts of water. DO NOT INDUCE VOMITING. FIRE AND SPILLS: For fire, use water fog, CO2, foam or dry chemicals to extinguish. For spills, shut off ignition sources, ventilate confined areas and wipe up with absorbent materials to prevent footing hazard. STORAGE AND HANDLING: Store in cool place away from all food. Keep container upright and tightly closed when not in use. Do not reuse empty container. KEEP OUT OF REACH OF CHILDREN.

    For additional information, refer to Material Safety Data Sheet.

    Top of Page

    LIMITED WARRANTY:


    RectorSeal® makes the Limited Express Warranty that when the instructions for storage and handling of our products are followed we warrant our products to be free from defects.  THIS LIMITED EXPRESS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER EXPRESS OR IMPLIED WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, AND OF ANY OTHER OBLIGATION ON THE PART OF RECTORSEAL®. The sole remedy for breach of the Limited Express Warranty shall be the refund of the purchase price. All other liability is negated and disclaimed, and RectorSeal® shall not be liable for incidental or consequential damages.

    Top of Page

    MANUFACTURED IN U.S.A. BY

    RectorSeal®
    2601 Spenwick Drive • Houston, TX 77055 USA
    713-263-8001 • Fax 713-263-7577
    Toll-free 800-231-3345 • Fax 800-441-0051

    Back